S11/S13/S20/S22 10kV oil-immersed distribution transformers (50-4000kVA) are widely used in 10kV distribution networks for direct power supply to end users. Typical applications include rural township...
View MoreProduct Overview DC 1500V PVC insulated power cable is designed specifically for DC power transmission and distribution systems, suitable for DC power supply circuits with a rated voltage of 1500V (maximum operating voltage up to 1800V). This product typically uses a single-core copper conductor structure. Compared with AC cables, the conductor has no skin effect or proximity effect, requiring no complex divided conductors, resulting in more uniform current distribution. This cable adds flame-retardant and fire-resistant properties to standard PVC insulated power cables, enabling it to maintain safe operation for a specified period under fire conditions, meeting GB/T 19666 general rules for flame-retardant and fire-resistant cables.
Implementation Standards
|
Standard No. |
Standard Name |
Scope |
|
GB/T 12706.1-2020 |
Extruded insulated power cables and accessories for rated voltages from 1kV to 35kV |
General technical requirements for power cables |
|
GB/T 19666 |
General rules for flame-retardant and fire-resistant cables |
Flame-retardant and fire-resistant performance requirements |
|
GB/T 3956 |
Cable conductors |
Conductor structure and resistance requirements |
|
GB/T 5023 |
PVC insulated cables for rated voltages up to 450/750V |
PVC insulation material standard |
Products can also be manufactured per IEC standards (e.g., IEC 60332 series) for export and special project requirements.
Product Structure
1. Conductor: High-quality oxygen-free copper rod drawn into copper conductors with excellent conductivity and low resistivity. Available in Class 1 (solid), Class 2 (stranded), or Class 5 (flexible, multi-strand) conductors.
2. Insulation: High-quality PVC compound extruded uniformly over the conductor.
- Heat rating: max conductor working temperature 70°C
- Insulation resistance constant >= 36.7 MOhm·km at 20°C
- Flame-retardant type uses flame-retardant PVC (ZR-PVC)
3. Filling and wrapping: Flame-retardant filling material between insulated cores; outer wrapping with flame-retardant tape.
4. Inner lining (armored type): PVC or alkali-free glass fiber tape winding.
5. Armoring (optional): Steel tape armoring (double galvanized steel tape) or steel wire armoring.
6. Outer sheath: Flame-retardant PVC sheath.
For fire-resistant cables, mica tape is wrapped between conductor and insulation to maintain circuit integrity when the outer insulation is burned.
Model Designation
|
Model |
Description |
Notes |
|
ZR-VV |
Copper core flame-retardant PVC insulated PVC sheathed power cable |
Basic flame-retardant type |
|
ZR-VV22 |
Copper core flame-retardant PVC insulated steel tape armored power cable |
Flame-retardant with armoring |
|
NH-VV |
Copper core fire-resistant PVC insulated PVC sheathed power cable |
Fire-resistant type |
|
NH-VV22 |
Copper core fire-resistant PVC insulated steel tape armored power cable |
Fire-resistant with armoring |
|
ZR-VV-1.5kV DC |
Copper core flame-retardant PVC insulated DC power cable |
Specified DC application |
Code meanings: ZR - Flame-retardant; NH - Fire-resistant; V - PVC insulation; V - PVC sheath; 22 - Steel tape armored PVC sheath.
Main Technical Parameters
Rated voltage: DC 1500V; Maximum operating voltage: 1800V.
Conductor DC resistance (20°C) - selected values:
- 10 mm²: <= 1.83 Ohm/km
- 50 mm²: <= 0.387 Ohm/km
- 120 mm²: <= 0.153 Ohm/km
- 240 mm²: <= 0.0754 Ohm/km
- 500 mm²: <= 0.0366 Ohm/km
Temperature characteristics:
- Max long-term conductor temperature: 70°C
- Short-circuit temperature (<=5s): 160°C (section <= 300 mm²) / 140°C (> 300 mm²)
- Minimum laying temperature: 0°C (preheat if below)
Bending radius: Non-armored >= 6D; armored >= 12D (D = cable OD)
Flame-retardant performance: Single vertical burning per GB/T 18380.12; bundled burning Grades A, B, C per GB/T 18380.33-35. Char height <= 2.5m (Grade A).
Fire-resistant performance: 750°C to 800°C for 90 min continuous power supply under rated voltage.
Application Areas
- Urban rail transit: Metro and light rail DC traction power supply
- Photovoltaic systems: DC side connections in solar power plants
- Energy storage systems: Battery module interconnections
- Industrial and commercial DC distribution
- Fire and emergency power supply systems (fire-resistant type)
| Model | Voltage level | Specification (number of cores x cross-sectional area) | Execution standard | Manufacturing branch |
| V(L)V62、V(L)V72 V(L)V63、V(L)V73 |
DC1500V | 1×4~1×800 | Q/320481SS563-2023 | 50mm² and below control cable factory Low voltage cable factory with an area of over 50mm² |
| V(L)V22 V(L)V32 V(L)V23 V(L)V33 |
2×1.5~2×300、3×1.5~3×300、 4×1.5~4×400、5×2.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×2.5+2×1.5~3×400+2×185、 4×2.5+1×1.5~4×400+1×185 |
6mm² and below control cable factory Low voltage cable factory with an area of 6mm² or more |
||
| V(L)V V(L)Y VRV VRY |
1×1.5~1×800、 (Among them, the five types of conductors have specifications ranging from 1 × 1.5 to 1 × 630) |
50mm² and below control cable factory Low voltage cable factory with an area of over 50mm² |
||
| 2×1.5~2×300、3×1.5~3×300 4×2.5~4×400、 3×2.5+1×1.5~3×400+1×185 5×2.5~5*400、 3×2.5+2×1.5~3×400+2×185、 4×2.5+1×1.5~4×400+1×185 |
6mm² and below control cable factory Low voltage cable factory with an area of 6mm² or more |
|||
| Z*-V(L)V62 Z*-V(L)V72 |
DC1500V | 1×4~1×800 | Q/320481SS563-2023 | 50mm² and below control cable factory Low voltage cable factory with an area of over 50mm² |
| Z*-V(L)V22 Z*-V(L)V32 Z*-V(L)V23 Z*-V(L)V33 |
2×1.5~2×300、3×1.5~3×300、 4×1.5~4×400、5×2.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×2.5+2×1.5~3×400+2×185、 4×2.5+1×1.5~4×400+1×185 |
6mm² and below control cable factory Low voltage cable factory with an area of 6mm² or more |
||
| Z*-V(L)V Z*-V(L)Y Z*-VRV Z*-VRY |
1×1.5~1×800 (Among them, the five types of conductors have specifications ranging from 1 × 1.5 to 1 × 630) |
50mm² and below control cable factory Low voltage cable factory with an area of over 50mm² |
||
| 2×1.5~2×300 3×1.5~3×300 4×2.5~4×400 3×2.5+1×1.5~3×400+1×185 5×2.5~5*400、 3×2.5+2×1.5~3×400+2×185、 4×2.5+1×1.5~4×400+1×185 |
6mm² and below control cable factory Low voltage cable factory with an area of 6mm² or more |
|||
| (Z*)N-VV62 (Z*)N-VV72 |
DC1500V | 1×4~1×800 | Q/320481SS563-2023 | 50mm² and below control cable factory Low voltage cable factory with an area of over 50mm² |
| (Z*)N-VV22 (Z*)N-VV32 (Z*)N-VV23 (Z*)N-VV33 |
2×1.5~2×300、3×1.5~3×300、 4×1.5~4×400、5×2.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×2.5+2×1.5~3×400+2×185、 4×2.5+1×1.5~4×400+1×185 |
6mm² and below control cable factory Low voltage cable factory with an area of 6mm² or more |
||
| (Z*)N-V(L)V (Z*)N-V(L)Y (Z*)N-VRV (Z*)N-VRY |
DC1500V | 1×1.5~1×800 (Among them, the five types of conductors have specifications ranging from 1 × 1.5 to 1 × 630) |
Q/320481SS563-2023 | 50mm² and below control cable factory Low voltage cable factory with an area of over 50mm² |
| 2×1.5~2×300、3×1.5~3×300 4×2.5~4×400、 3×2.5+1×1.5~3×400+1×185 5×2.5~5*400、 3×2.5+2×1.5~3×400+2×185、 4×2.5+1×1.5~4×400+1×185 |
6mm² and below control cable factory Low voltage cable factory with an area of 6mm² or more |
Hixon (Changzhou) Science and Technology Innovation Investment Co., Ltd. is located in Changzhou, Jiangsu, China. It is a comprehensive trading company specializing in the export of industrial products. With years of international trade experience, the company has established strong channel resources and project collaboration experience in the African market.
By integrating high-quality manufacturing resources with a well-established supply chain, we provide reliable product supply and professional trade services to global customers, aiming to become an important bridge connecting Chinese manufacturing to the global market.