S11/S13/S20/S22 10kV oil-immersed distribution transformers (50-4000kVA) are widely used in 10kV distribution networks for direct power supply to end users. Typical applications include rural township...
View MoreProduct Overview The insulation layer of this cable series utilizes cross-linked polyethylene (XLPE). Through chemical cross-linking (peroxide dry chemical or silane cross-linking) or irradiation cross-linking, the linear molecular structure of polyethylene is transformed into a three-dimensional network structure. This process increases the long-term allowable working temperature from 70°C (for ordinary polyethylene) to 90°C (and up to 250°C during short circuits), while providing superior mechanical and electrical properties. The sheath and auxiliary materials consist of halogen-free low-smoke flame-retardant polyolefin, which contains no halogens, produces minimal smoke during combustion, and releases no toxic or corrosive gases, making it a green and environmentally friendly product. For fire-resistant models (WDZN), a fire-resistant mica tape layer is added over the conductor to ensure the cable maintains normal power supply for a specified duration during a fire. These cables are widely used in densely populated areas such as high-rise buildings, subways, hospitals, schools, shopping malls, hotels, stations, chemical plants, and power stations. They are also essential for fire alarm systems, fire-fighting facilities, emergency systems, and other environments with high safety and environmental requirements.
Product Implementation Standards
Production primarily follows these national and industry standards:
- GB/T 12706.1-2020: Requirements for basic structure, dimensions, electrical, and mechanical properties of power cables.
- GB/T 19666-2019: General rules for flame retardant and fire resistant characteristics.
- GB/T 3956: Requirements for conductor DC resistance.
- GB/T 18380 (IEC 60332): Classification tests for flame retardant performance.
- GB/T 17650 (IEC 60754): Halogen-free performance (halogen acid gas evolution).
- GB/T 17651 (IEC 61034): Low-smoke performance (smoke density/light transmittance).
Meaning of Model Codes
Models are composed of the following code combinations:
- Characteristics: WDZ / WDZA / WDZB / WDZC / WDZN — LSZH Flame-retardant (Grades A/B/C) / LSZH Flame-retardant Fire-resistant.
- Conductor: T (omitted) / L — Copper / Aluminum.
- Insulation: YJ — Cross-linked polyethylene (XLPE).
- Sheath: Y — Polyolefin sheath (LSZH material).
- Armoring (Optional): 23 / 33 / 63 / 73 — Double steel tape / Fine steel wire / Double non-magnetic metal tape / Non-magnetic metal wire.
Product Cross-section and Specification Range
Utilizing Class 1 (solid) or Class 2 (stranded) copper conductors:
- 1-Core: 1.5 to 1000 mm²
- 2-Core: 1.5 to 400 mm²
- 3-Core: 1.5 to 400 mm² (including 3+1 or 3+2 configurations)
- 4-Core: 1.5 to 400 mm² (including 4+1 configurations)
- 5-Core: 1.5 to 400 mm²
Main Performance Parameters
1. Electrical: Rated voltage 0.6/1 kV, maximum system voltage 1.2 kV, AC voltage test 3.5 kV / 5 min without breakdown.
2. Temperature: Max long-term working temperature +90°C, short-circuit temperature (max 5s) +250°C.
3. Mechanical: Minimum bending radius is 20D for unarmored single-core and 15D for multi-core cables.
4. Fire Performance: Meets halogen-free (low acidity/conductivity) and low-smoke (high light transmittance) requirements. Fire resistance (WDZN) supports Grade A (950-1000°C) or Grade B (750-800°C) for 90 minutes.
Usage Conditions
Suitable for AC 50Hz, 1kV and below power lines. It supports various installation methods including pipe, trench, tunnel, overhead, or direct burial. Armored models are recommended for environments with high mechanical loads.
Application Scenarios
- High-rise buildings and malls: WDZA/WDZB-YJY or WDZN-YJY.
- Hospitals and schools: WDZB/WDZC-YJY.
- Subways and tunnels: WDZA-YJY or WDZN-YJY23.
- Fire and emergency systems: WDZN-YJY.
Inspection and Acceptance Rules
Cables undergo routine tests (R) for every manufactured length, sample tests (S) for structural and mechanical checks, and comprehensive type tests (T) to ensure all specified requirements are met before supply.
Environmental Protection and Safety Characteristics
- Halogen-Free: Releases no toxic corrosive gases like hydrogen chloride.
- Low-Smoke: High light transmittance facilitates emergency escape and rescue.
- Low-Toxicity: Complies with the low toxicity requirements of GB/T 19666.
- Flame-Retardant: Effectively inhibits the spread of fire and self-extinguishes once the fire source is removed.
| Model | Voltage level | Specification (number of cores x cross-sectional area) | Execution standard | Manufacturing branch |
| WDZ*-YJY63 WDZ*-YJY73 |
0.6/1kV | 1×4~1×1000 | GB/T 12706.1-2020 Non-standard model execution Q/320481SS005-2024 |
50mm²and the following special cable production plants 50mm² The above low-voltage cable factory |
| WDZ*-YJY23 WDZ*-YJY33 WDZ*-YJLY23 WDZ*-YJLY33 |
2×1.5~2×400、3×1.5~3×400、 4×1.5~4×400、5×1.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×4+2×2.5~3×400+2×185、 4×4+1×2.5~4×400+1×185 |
6mm²and the following special cable production plants 6mm² The above low-voltage cable factory |
||
| WDZ*-YJY WDZ*-YJRY WDZ*-YJLY |
1×1.5~1×1000 (WDZ * - YJRY specifications range from 1 × 1.5 to 1 × 630) |
50mm²and the following special cable production plants 50mm² The above low-voltage cable factory |
||
| 2×1.5~2×400 3×1.5~3×400、4×1.5~4×400、 5×1.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×4+2×2.5~3×400+2×185、 4×4+1×2.5~4×400+1×185 |
6mm²and the following special cable production plants 6mm² The above low-voltage cable factory |
|||
| WDZ*N-YJY63 WDZ*N-YJY73 |
0.6/1kV | 1×4~1×1000 | GB/T 12706.1-2020 GB/T 19666-2019 Non-standard model execution Q/320481SS005-2024 |
50mm²and the following special cable production plants 50mm² The above low-voltage cable factory |
| WDZ*N-YJY23 WDZ*N-YJY33 |
2×1.5~2×400、3×1.5~3×400、 4×1.5~4×400、5×1.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×4+2×2.5~3×400+2×185、 4×4+1×2.5~4×400+1×185 |
6mm²and the following special cable production plants 6mm² The above low-voltage cable factory |
||
| WDZ*N-YJY WDZ*N-YJRY |
0.6/1kV | 1×1.5~1×1000 (Among them, WDZ * N-YJRY specifications range from 1 × 1.5 to 1 × 630) |
50mm²and the following special cable production plants 50mm² The above low-voltage cable factory |
|
| 2×1.5~2×400 3×1.5~3×400、4×1.5~4×400、 5×1.5~5×300、 3×2.5+1×1.5~3×400+1×185、 3×4+2×2.5~3×400+2×185、 4×4+1×2.5~4×400+1×185 |
6mm²and the following special cable production plants 6mm² The above low-voltage cable factory |
Hixon (Changzhou) Science and Technology Innovation Investment Co., Ltd. is located in Changzhou, Jiangsu, China. It is a comprehensive trading company specializing in the export of industrial products. With years of international trade experience, the company has established strong channel resources and project collaboration experience in the African market.
By integrating high-quality manufacturing resources with a well-established supply chain, we provide reliable product supply and professional trade services to global customers, aiming to become an important bridge connecting Chinese manufacturing to the global market.