S11/S13/S20/S22 10kV oil-immersed distribution transformers (50-4000kVA) are widely used in 10kV distribution networks for direct power supply to end users. Typical applications include rural township...
View MoreProduct Introduction Cross-linked polyethylene (XLPE) insulated power cable uses chemical or physical cross-linking to transform linear polyethylene into a three-dimensional network structure. XLPE insulation offers outstanding electrical, mechanical, heat aging, environmental stress, and chemical corrosion resistance. The cable is simple in structure, easy to use, has no restriction on laying height difference, and provides high long-term operating temperature and large transmission capacity. This product is suitable for 6~35kV power transmission and distribution systems, used as the power carrier for transmission and distribution lines in electric power, construction, mining, metallurgy, petroleum, chemical, and transportation sectors. It has completely replaced oil-impregnated paper insulated cables and partially replaced PVC insulated cables. This series features both flame-retardant and anti-termite properties, making it especially suitable for fire alarm systems, firefighting facilities, emergency evacuation systems, as well as direct burial in southern regions with severe termite damage.
Implementation Standards
Core standard: GB/T 12706 (equivalent to IEC 60502) for design and manufacture.
- GB/T 12706.2: For rated voltages 6kV to 30kV
- GB/T 12706.3: For rated voltage 35kV
- GB/T 19666: Flame-retardant grade standard
- GB/T 18380 (equivalent to IEC 60332): Flame-retardant test
- IEC 60754: Combustion gas corrosivity test
- JB/T 10696.9-2011: Anti-termite test methods
Product Structure
1. Conductor: High-purity oxygen-free copper (T) or aluminum (L); compact round stranded; single-core 25 to 2000 mm², three-core 25 to 400 mm²
2. Conductor shield: Semiconductive layer extruded on conductor surface (3.6/6kV and above)
3. Insulation: XLPE; chemical or irradiation cross-linking; high strength, low dielectric loss
4. Insulation shield: Semiconductive material; capacitive shielding with metal shield
5. Metal shield (optional): Copper tape or copper wire
6. Filling and cabling: Non-hygroscopic filling ropes
7. Armoring (model-dependent):
- Code 22: Double steel tape — for direct burial
- Code 32: Fine steel wire — for vertical installation
- Code 42: Thick steel wire — for underwater/large tensile force
- Code 23/33/43: With polyethylene outer sheath for improved waterproofing
8. Sheath and anti-termite design (three-layer protection):
- Outer sheath chemical repellent: Eco-friendly repellent (e.g., capsaicin, camphor) in sheath material
- Armoring physical barrier: Steel tape/wire blocks termite penetration
- Inner sheath protection: Anti-termite components as final barrier
Technical Parameters
Rated voltage range:
- 3.6/6 kV, 6/6 kV, 6/10 kV, 8.7/10 kV, 8.7/15 kV, 12/20 kV, 18/30 kV, 21/35 kV, 26/35 kV
Electrical performance:
- Conductor DC resistance (20°C): per GB/T 3956
- Insulation resistance constant (90°C): >= 3.67 MOhm·km
- Partial discharge: <= 5pC at 1.73U0
- Max long-term conductor temperature: 90°C
- Short-circuit temperature (<=5s): 250°C
- Overload temperature: 130°C
Bending radius: Single-core unarmored 20D; armored 15D; three-core unarmored 15D; armored 12~13D.
Flame-retardant and Anti-termite Models
|
Model |
Description |
|
ZR-* |
Flame-retardant type; grades ZA, ZB, ZC |
|
WDZR-* |
LSZH flame-retardant type |
|
FY-YJV22 |
Steel tape armored anti-termite power cable |
|
MFY-YJV(Y) |
Anti-termite XLPE power cable |
|
WDZR-FSY-YJY23 |
LSZH flame-retardant rodent/termite-resistant armored cable |
Anti-termite test per JB/T 10696.9-2011: test temperature 27±2°C, duration over 3 months; Grade I protection achieved.
Application Areas
- Direct burial in termite-prone areas (recommended armored type)
- Fire alarm, firefighting, and emergency evacuation distribution systems
- Electric power, construction, mining, metallurgy, petroleum, and chemical sectors
- Underground facilities, tunnels, high-rise buildings, nuclear power plants (LSZH type)
Service life: >= 30 years under normal installation conditions.
| Model | Voltage level | Specification (number of cores x cross-sectional area) | Execution standard | Manufacturing branch |
| YJ(L)V、YJ(L)Y、 YJ(L)V22(32、42)、YJ(L)Y22(32、42)、 YJ(L)V23(33、43)、YJ(L)Y23(33、43)、 YJ(L)V(62、72)、YJ(L)Y(62、72)、 YJ(L)V(63、73)、YJ(L)Y(63、73)、 YJ(L)SV、YJ(L)SY、 YJ(L)SV22(32、42)、YJ(L)SY22(32、42)、 YJ(L)SV23(33、43)、YJ(L)SY23(33、43)、 YJ(L)SV(62、72)、YJ(L)SY(62、72)、 YJ(L)SV(63、73)、YJ(L)SY(63、73) |
3.6/6kV、6/6kV、 6/10kV、8.7/10kV、8.7/15kV |
1×25~1×1000 3×25~3×500 | GB/T 12706-2020 |
Medium Voltage Cable Factory |
| 12/20kV | 1×35~1×1000 3×35~3×500 | Medium Voltage Cable Factory | ||
| 18/20kV、18/30kV、21/35kV、26/35kV | 1×50~1×1000 3×50~3×500 | Medium Voltage Cable Factory | ||
| Z(A、B、C)-YJ(L)V、 Z(A、B、C)-YJ(L)Y、 Z(A、B、C)-YJ(L)V22(32、42)、 Z(A、B、C)-YJ(L)Y22(32、42)、 Z(A、B、C)-YJ(L)V23(33、43)、 Z(A、B、C)-YJ(L)Y23(33、43)、 Z(A、B、C)-YJ(L)V(62、72)、 Z(A、B、C)-YJ(L)Y(62、72)、 Z(A、B、C)-YJ(L)V(63、73)、 Z(A、B、C)-YJ(L)Y(63、73)、 Z(A、B、C)-YJ(L)SV、 Z(A、B、C)-YJ(L)SY、 Z(A、B、C)-YJ(L)SV22(32、42)、 Z(A、B、C)-YJ(L)SY22(32、42)、 Z(A、B、C)-YJ(L)SV23(33、43)、 Z(A、B、C)-YJ(L)SY23(33、43)、 Z(A、B、C)-YJ(L)SV(62、72)、 Z(A、B、C)-YJ(L)SY(62、72)、 Z(A、B、C)-YJ(L)SV(63、73)、 Z(A、B、C)-YJ(L)SY(63、73) |
3.6/6kV、6/6kV、 6/10kV、 8.7/10kV、8.7/15kV |
1×25~1×1000 3×25~3×500 | GB/T 12706-2020 |
Medium Voltage Cable Factory |
| 12/20kV | 1×35~1×1000 3×35~3×500 | Medium Voltage Cable Factory | ||
| 18/20kV、18/30kV、21/35kV、26/35kV | 1×50~1×1000 3×50~3×500 | Medium Voltage Cable Factory | ||
| ZR(A、B、C)-YJ(L)V、ZR(A、B、C)-YJ(L)Y、 ZR(A、B、C)-YJ(L)V22(32、42)、 ZR(A、B、C)-YJ(L)Y22(32、42)、 ZR(A、B、C)-YJ(L)V23(33、43)、 ZR(A、B、C)-YJ(L)Y23(33、43)、 ZR(A、B、C)-YJ(L)V(62、72)、 ZR(A、B、C)-YJ(L)Y(62、72)、 ZR(A、B、C)-YJ(L)V(63、73)、 ZR(A、B、C)-YJ(L)Y(63、73)、 ZR(A、B、C)-YJ(L)SV、ZR(A、B、C)-YJ(L)SY、 ZR(A、B、C)-YJ(L)SV22(32、42)、 ZR(A、B、C)-YJ(L)SY22(32、42)、 ZR(A、B、C)-YJ(L)SV23(33、43)、 ZR(A、B、C)-YJ(L)SY23(33、43)、 ZR(A、B、C)-YJ(L)SV(62、72)、 ZR(A、B、C)-YJ(L)SY(62、72)、 ZR(A、B、C)-YJ(L)SV(63、73)、 ZR(A、B、C)-YJ(L)SY(63、73) |
3.6/6kV、6/6kV、 6/10kV、 8.7/10kV、8.7/15kV |
1×25~1×1000 3×25~3×500 | Q/320481SS019-2024 |
Medium Voltage Cable Factory |
| 12/20kV | 1×35~1×1000 3×35~3×500 | Medium Voltage Cable Factory | ||
| 18/20kV、18/30kV、21/35kV、26/35kV | 1×50~1×1000 3×50~3×500 | Medium Voltage Cable Factory | ||
| (FY)-YJ(L)V、(FY)-YJ(L)Y、 (FY)-YJ(L)V22(32、42)、 (FY)-YJ(L)V23(33、43)、 (FY)-YJ(L)Y22(32、42)、 (FY)-YJ(L)Y23(33、43)、 (FY)-YJ(L)SV、(FY)-YJ(L)SY、 (FY)-YJ(L)SV22(32、42)、 (FY)-YJ(L)SV23(33、43)、 (FY)-YJ(L)SY22(32、42)、 (FY)-YJ(L)SY23(33、43)、 (FY)-YJ(L)V(62、72)、(FY)-YJ(L)Y(62、72)、 (FY)-YJ(L)V(63、73)、(FY)-YJ(L)Y(63、73) |
3.6/6kV、6/6kV、 6/10kV、 8.7/10kV、8.7/15kV |
1×25~1×1000 3×25~3×500 | Q/320481SS019-2024 | Medium Voltage Cable Factory |
| Medium Voltage Cable Factory | ||||
| Medium Voltage Cable Factory | ||||
| 12/20kV | 1×35~1×1000 3×35~3×500 | Medium Voltage Cable Factory | ||
| 18/20kV、18/30kV、21/35kV、26/35kV | 1×50~1×1000 3×50~3×500 | Medium Voltage Cable Factory | ||
| Medium Voltage Cable Factory |
Hixon (Changzhou) Science and Technology Innovation Investment Co., Ltd. is located in Changzhou, Jiangsu, China. It is a comprehensive trading company specializing in the export of industrial products. With years of international trade experience, the company has established strong channel resources and project collaboration experience in the African market.
By integrating high-quality manufacturing resources with a well-established supply chain, we provide reliable product supply and professional trade services to global customers, aiming to become an important bridge connecting Chinese manufacturing to the global market.