S11/S13/S20/S22 10kV oil-immersed distribution transformers (50-4000kVA) are widely used in 10kV distribution networks for direct power supply to end users. Typical applications include rural township...
View MoreProduct Overview Rated voltage 0.6/1kV low-smoke halogen-free Grade B1 low-toxicity power cable is an environmentally friendly flame-retardant power cable designed for densely populated areas and buildings with high fire safety requirements. The product uses XLPE insulation and low-smoke halogen-free flame-retardant polyolefin sheath, providing comprehensive halogen-free, low-smoke, flame-retardant, and low-toxicity performance. It is an upgraded replacement for traditional PVC-insulated cables. This cable has been widely applied in nuclear power plants, metro systems, airports, theaters, super high-rise buildings, hospitals, schools, and other important facilities with high safety requirements.
Implementation Standards
|
Standard No. |
Standard Name |
Main Content |
|
GB/T 12706.1-2020 |
Extruded insulated power cables for rated voltages 1kV to 35kV |
Cable structure, dimensions, and electrical performance |
|
GB 31247-2014 |
Combustion performance classification of cables |
B1 grade determination and additional information (d0, t0, a1) |
|
GB/T 19666-2019 |
General rules for flame-retardant and fire-resistant cables |
Technical requirements for halogen-free, low-smoke, low-toxicity, flame-retardant, fire-resistant properties |
Common Models and Code Meanings
Typical models: WDZB1-YJY, WDZB1-YJY23 (steel tape armored), WDZB1N-YJY (with fire-resistant property).
Code meanings:
- W: Halogen-free — no halogen elements (F, Cl, Br, I, At) in sheath
- D: Low-smoke — extremely low smoke density during combustion
- Z: Flame-retardant
- B1: Grade B1 per GB 31247-2014
- N: Fire-resistant (when required)
- YJ: XLPE insulation; Y: polyolefin sheath
Main Technical Parameters
Electrical performance:
- Rated voltage U0/U: 0.6/1 kV; Max system voltage Um: 1.2 kV
- AC voltage test: 3500V / 5 min without breakdown
- Insulation resistance >= 1000 MOhm·km
Temperature parameters:
- Max long-term conductor temperature <= 90°C
- Short-circuit temperature (<=5s): 250°C
- Laying temperature >= 0°C (preheat if below 0°C)
- Operating temperature: -40°C to +50°C
Bending radius (D = OD): Unarmored single-core >= 20D; unarmored multi-core >= 15D; armored single-core >= 12D; armored multi-core >= 10D
Grade B1 Combustion Performance
Per GB 31247-2014, Grade B1 cables must pass stringent tests:
|
Test Indicator |
Requirement |
|
Flame Spread (FS) |
<= 1.5 m |
|
Peak Heat Release Rate |
<= 30 kW |
|
Total Heat Release (1200s) |
<= 15 MJ |
|
Fire Growth Rate Index (FIGRA) |
<= 150 W/s |
|
Peak Smoke Production Rate |
<= 0.25 m²/s |
|
Total Smoke Production (1200s) |
<= 50 m² |
|
Smoke Density (min. transmittance) |
>= 60% |
Additional classification (mandatory for B1 grade):
- Flaming droplets/particles: d0 (no droplets in 1200s) typical for B1
- Smoke toxicity: t0 (ZA2 grade) typical for B1
- Corrosivity: a1 (low corrosivity) typical for B1
Per DGJ08-2048-2016 and GB 50016-2018: Super high-rise buildings must select cables with combustion Grade B1 or above, toxicity t0, droplet grade d0.
Product Structure
1. Conductor: Oxygen-free copper rod, resistivity < 0.01700 Ohm·mm²/m
2. Insulation: XLPE — chemically cross-linked from linear PE to 3D network structure
3. Filling and oxygen barrier: Metal hydrates (magnesium hydroxide) release crystalline water to lower flame temperature
4. Armoring (YJY23): Double-layer galvanized steel tape gap winding
5. Sheath: Low-smoke halogen-free high-resistance polyolefin
Application Areas
|
Application Area |
Typical Locations |
|
Urban construction |
High-rise, super-high-rise buildings, large commercial complexes |
|
Public transportation |
Metro, light rail, airports, stations |
|
Public facilities |
Hospitals, schools, convention centers, stadiums |
|
Critical facilities |
Data centers, financial centers, telecom hubs, power dispatch centers |
|
Special venues |
Hotels, theaters, shopping malls, nuclear power plants |
| Model | Voltage level | Specification (number of cores x cross-sectional area) | Execution standard | Manufacturing branch |
| WDUZB1(N)-YJY WDUZ*(N)-YJY-B1 |
0.6/1kV | 1×1.5~1×800 | Q/320481SS577-2024 | 50mm² and below special cable factory Low voltage cable factory with an area of over 50mm² |
| WDUZB1(N)-YJY WDUZ*(N)-YJY-B1 WDUZB1(N)-YJY23 WDUZ*(N)-YJY23-B1 |
0.6/1kV | 2×1.5~2×400 3×1.5~3×400 4×1.5~4×400 5×1.5~5×400 3×2.5+1×1.5~3×400+1×185 3×4+2×2.5~3×400+2×185 4×4+1×2.5~4×400+1×185 |
Special cable factory of 6mm² and below Low voltage cable factory with an area of 6mm² or more |
Hixon (Changzhou) Science and Technology Innovation Investment Co., Ltd. is located in Changzhou, Jiangsu, China. It is a comprehensive trading company specializing in the export of industrial products. With years of international trade experience, the company has established strong channel resources and project collaboration experience in the African market.
By integrating high-quality manufacturing resources with a well-established supply chain, we provide reliable product supply and professional trade services to global customers, aiming to become an important bridge connecting Chinese manufacturing to the global market.